Abstract:
The objective of this study is to present the test
results of variable air volume (VAV) air conditioning system
optimized by two objective genetic algorithm (GA). The objective
functions are energy savings and thermal comfort. The optimal set
points for fuzzy logic controller (FLC) are the supply air temperature
(T
s
), the supply duct static pressure (P
s
), the chilled water
temperature (T
w
), and zone temperature (T
z
) that is taken as the
problem variables. Supply airflow rate and chilled water flow rate are
considered to be the constraints. The
optimal set point values are
obtained from GA process and assigned into fuzzy logic controller
(FLC) in order to conserve energy and maintain thermal comfort in
real time VAV air conditioning system. A VAV air conditioning
system with FLC installed in a software laboratory has been taken for
the purpose of energy analysis. The total energy saving obtained in
VAV GA optimization system with FLC compared with constant air
volume (CAV) system is expected to achieve 31.5%. The optimal
duct static pressure obtained through Genetic fuzzy methodology
attributes to better air distribution by delivering the optimal quantity
of supply air to the conditioned space. This combination enhanced
the advantages of uniform air distribution, thermal comfort and
improved energy savings potential