Abstract:
A frequency dependent approach to defining a dynamic relative gain array (DRGA) is discussed. The approach assumes the availability of a dynamic transfer function based process model for control loop pairing analysis. Two examples are considered: one in which the traditional RGA (based on steady-state gain matrix) gives the correct pairing recommendation and the other in which the traditional RGA suggests wrong pairings particularly in the frequency range of interest. The calculations pertaining to analysis of control loop pairing is performed using MATLAB (version 7.0.1). An inaccurate indication of the amount of interaction present is discussed