Abstract:
In this paper, a new Power Angle Control (PAC) method for Unified Power Quality Conditioner with Distributed Generation (UPQC DG ) is proposed for effective grid integration of solar PV. In UPQC DG shunt Active Power Filter (APF) feeds power from solar PV to load, apart from supplying reactive power demand, leading to increased rating of shunt APF. PAC method aims at effective utilization of series and shunt APFs of UPQC DG to reduce their ratings. In this work a new power angle estimation method based on instantaneous power calculation is proposed. Proposed estimation technique is simple, robust and utilizes already available measurements of UPQC DG . Performance of proposed system is tested in the presence of non-linear and reactive loads with detailed model of solar PV generation system. Dynamic performance of system is studied during grid disturbances such as voltage sag and swell, solar irradiation variation, and change in load. MATLAB/Simulink based simulations validate effectiveness of proposed method.