Study on various hot-gas defrosting configurations for CO2-NH3 cascade deep freezer

dc.contributor.authorDasgupta, Mani Sankar
dc.date.accessioned2025-10-09T07:05:55Z
dc.date.available2025-10-09T07:05:55Z
dc.date.issued2024
dc.description.abstractFour hot-gas bypass defrosting configurations for CO2-NH3 cascade blast freezer for application in fish processing firm are numerically investigated. Due to the high moisture content of fish, defrosting is necessary after every 4 to 5 h of batch operation. A thermodynamic model for the cascade system and defrosting was developed to study various defrosting configurations formulated by rearranging the existing compressor to operate as a defrosting compressor and with the addition of an external defrosting compressor. From the simulation findings, it can be summarized that the conventional hot-gas bypass defrosting without defrost compressor is suitable for a high-capacity cascade refrigeration system with more than three evaporators. For low cooling capacity refrigeration systems, a defrosting compressor is necessary to elevate the temperature above the cascade condensing temperature. A dedicated defrosting compressor with a power consumption of 3.1 kW and a modified refrigeration/defrosting compressor with a power consumption of 6.8 kW can deliver 33.3 kW of heating at a temperature of +10 °C (45 bar). Incorporating a desuperheater between the main and defrosting compressors reduces compressor temperature and maintains the lubricating oil stability, without change in defrosting energy consumption and less exergy loss. The defrosting efficiency is obtained in the range of 39.7–42% which is in agreement with published literature.en_US
dc.identifier.urihttps://link.springer.com/article/10.1007/s44189-024-00049-9
dc.identifier.urihttp://dspace.bits-pilani.ac.in:8080/jspui/handle/123456789/19694
dc.language.isoenen_US
dc.publisherSpringeren_US
dc.subjectMechanical engineeringen_US
dc.subjectCO2-NH3 cascade refrigerationen_US
dc.subjectHot-gas bypass defrostingen_US
dc.subjectFish processing blast freezeren_US
dc.subjectThermodynamic defrosting modelen_US
dc.titleStudy on various hot-gas defrosting configurations for CO2-NH3 cascade deep freezeren_US
dc.typeArticleen_US

Files